SINGLE PHASE STATIC INVERTERS

The BLE EPS-II range of static inverter units are designed to comply with the latest European and British Standard BS EN 50171:2001 for emergency lighting central systems. The Inverters are manufactured to a high standard, providing a cost effective integrated solution for emergency power for escape and emergency lighting systems where a minimum of 3 hours autonomy and less than 24 hours full recharging is required (other standby durations available on request). The units are designed with simplicity in mind, both for the end user and the maintenance provider; whether that is the battery configuration or accessibility for periodic maintenance works.

Features:

  • Ideal for Emergency Lighting applications
  • Compact design for ease of installation in restricted space
  • Digital System Status Display
  • 230V
  • 1.6-16.6KVA
  • 1 year guarantee

Specifications

Specification - Input:

  • Voltage: 230V AC +/- 10%
  • THD (Linear Load): <5%
  • Frequency: 50Hz +/- 5%
  • Phase: Single Phase
  • Max Input Current: (Watts/230) x 1.35 = Amps

 

Specification - Output:

  • Rated Voltage: 230V AC
  • Phase: Single Phase
  • Frequency Stability: <+/- 0.5% (Asynchronus)
  • Frequency Stability: <+/- 2% (Synchronous)
  • Crest Factor: 3:1
  • Output Wave Form: Pure Sine Wave
  • Voltage Transfer: 0-100%, Dynamic Load: 100%
  • Overload Capacity: 20% continuously for >1 hour
    150% continuously for 10 minutes
    200% continuously for <1 minute
  • Efficiency: (100% Load) >90%
  • Load PF: >0.70
  • Operating Temperature: 0-25ºC (other options available)
  • Relative Humidity: 30-90% Non-condensing
  • Altitude: <1000m
  • Noise: 45-65dBA
  • Colour: Blue / Grey